California Building Code

Amendment Effective April 1, 1998 

706.1a General: Construction joints installed in or between fire-resistive walls, fire-resistive-floors or floor-ceiling assemblies and fire-resistive roof or floor-ceiling assemblies shall be protected by an approved fire-resistive joint system designed to resist the passage of fire for a time period not less than the required fire-resistive rating of the floor, roof or wall in or between which it is installed. Fire-resistive joint systems shall be tested in accordance with Section 706.2

Such material or construction assembly shall be securely installed in or on the joint for its entire length so as not to dislodge, loosen or otherwise impair its ability to accommodate expected building movements and to resist the spread of fire and hot gases.

706.2a Fire-resistive Joint Systems: Fire-resistive joint systems shall be tested in accordance with UBC Standard 7.1 under the following conditions:

. 1. The joint systems shall be inserted full height in wall assemblies and full length in floor and roof assemblies.

2. Floor and roof assemblies shall be tested with a minimum positive pressure differential of 0.01 inch of water column (2.5 Pa)\

3. Wall assemblies shall be tested with a minimum positive pressure differential of 0.01 inch of water column (2.5 Pa) measured at the mid- height of the wall assembly.

4. Joint systems shall contain a splice. For wall assemblies the splice shall be located above the mid-height of the wall.

5. Joint systems shall be tested at the maximum joint width for which they are designed Joint Systems designed to accommodate movement shall be expanded to the maximum joint opening width for which they are intended to function.

 
 